基于局部放電測試技術(shù)的避雷器狀態(tài)診斷方法研究
DOI:
CSTR:
作者:
作者單位:

寧波送變電建設有限公司

作者簡(jiǎn)介:

通訊作者:

中圖分類(lèi)號:

基金項目:


Research on Condition Diagnosis Method of Arrester Based on partial discharge Testing Technology
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 圖/表
  • |
  • 訪(fǎng)問(wèn)統計
  • |
  • 參考文獻
  • |
  • 相似文獻
  • |
  • 引證文獻
  • |
  • 資源附件
  • |
  • 文章評論
    摘要:

    避雷器經(jīng)過(guò)長(cháng)時(shí)間使用或受到外界環(huán)境的影響,可能會(huì )出現老化、損壞或失效的情況,影響避雷器狀態(tài)診斷準確性,為保證避雷器狀態(tài)的帶電診斷性能,提出基于局部放電測試技術(shù)的避雷器狀態(tài)診斷方法。模擬內部氣隙、尖刺、沿面等局部放電現象的產(chǎn)生過(guò)程,確定不同局部放電狀態(tài)下避雷器的運行特征,以此作為避雷器狀態(tài)診斷標準。優(yōu)化設計避雷器局部放電信號采集設備,利用該設備采集避雷器的實(shí)時(shí)狀態(tài)信號,從統計和時(shí)頻域兩個(gè)方面,提取避雷器運行狀態(tài)特征。利用局部放電測試技術(shù),計算避雷器放電參數,通過(guò)特征匹配度和放電參數的比對,得出避雷器狀態(tài)的診斷結果。實(shí)驗結果表明,在200kV和500kV避雷器中,所提方法平均局部放電量診斷誤差分別為0.5pc和1.0pc,局部放電相位幅值診斷誤差0.01V和0.01V,狀態(tài)診斷準確率平均值為99.5%和99.6%。

    Abstract:

    After prolonged use or exposure to external environmental influences, lightning arresters may experience aging, damage, or failure, which affects the accuracy of lightning arrester status diagnosis. To ensure the live diagnosis performance of lightning arrester status, a lightning arrester status diagnosis method based on partial discharge testing technology is proposed. Simulate the generation process of internal air gap, spike, surface and other partial discharge phenomena, determine the operation characteristics of the arrester under different partial discharge conditions, and take this as the diagnosis standard of the arrester status. Optimize the design of partial discharge signal acquisition equipment for lightning arresters, use this equipment to collect real-time status signals of lightning arresters, and extract operational status characteristics of lightning arresters from both statistical and time-frequency domain aspects. Using partial discharge testing technology, calculate the discharge parameters of the lightning arrester, and obtain the diagnostic results of the lightning arrester status through the comparison of feature matching and discharge parameters. The experimental results show that in 200kV and 500kV lightning arresters, the average diagnostic errors of the proposed method for partial discharge quantity are 0.5pc and 1.0pc, respectively, and the diagnostic errors for partial discharge phase amplitude are 0.01V and 0.01V. The average accuracy of state diagnosis is 99.5% and 99.6%.

    參考文獻
    相似文獻
    引證文獻
引用本文

江熠,金坤鵬,錢(qián)錫穎,任一舟.基于局部放電測試技術(shù)的避雷器狀態(tài)診斷方法研究計算機測量與控制[J].,2024,32(7):36-43.